SIGN IN YOUR ACCOUNT TO HAVE ACCESS TO DIFFERENT FEATURES

Want an easier way to log in?

Log in faster without a password.

Email Magic Link

Use Your Passkey

Or

Log in with your password

Log in without a password

For security, use of Google's reCAPTCHA service is required which is subject to the Google Privacy Policy and Terms of Use.

I agree to these terms.

FORGOT YOUR PASSWORD?

FORGOT YOUR DETAILS?

AAH, WAIT, I REMEMBER NOW!

APC UPS

  • PRODUK
    • UPS
      • Easy UPS
      • Backup UPS
      • Smart UPS (Line Interactive)
      • Medium-Smart-Online
      • SRT & Li-Ion
      • SMV
    • Power Distribution
      • Rack Power Distribution
    • Data Center Software
      • Monitoring and Control
      • Modelling and Planning
      • Operations
      • Software Services
    • Prefabricated Data Center Modules
      • Cooling Modules
      • Power Modules
      • IT Modules
    • Cooling
      • Room Air Conditioners
      • Close Coupled Air Conditioners
      • Chillers
      • Containment and Air Distribution
      • Modular Access Floor
      • Cooling Distribution and Piping
      • Air Economizers
    • Surge Protection and Power Conditioning
      • Surge Protection Devices
      • Voltage Regulators
    • Networking and Cable Solutions
      • Networking Cables and Adapters
    • Data Centers and Server Rooms and Network Closets
      • InfraStruxure for Server Rooms and Network Closets
      • Modular Systems
    • Symmetra
    • Accessories
      • Mobile Accessories
        • Portable Devices Charger
      • NMC
      • RBC
  • LAYANAN
    • Install
    • Operate
    • Maintenance
    • Battery Replacement Service
    • Renew
    • Extended Warranties
  • Youtube Channel
  • Contact US
  • Join Reseller
  • Blog
HUBUNGI KAMI!
  • Home
  • Blog APC Indonesia
  • Berita
  • Mengapa Lampu LED Baterai Berkedip di APC Smart-UPS?
 

Mengapa Lampu LED Baterai Berkedip di APC Smart-UPS?

Mengapa Lampu LED Baterai Berkedip di APC Smart-UPS?

by Davin / Senin, 23 Juni 2025 / Published in Berita
led baterai berkedip apc-ups.id

Produk:
Semua model APC Smart-UPS dan Smart-UPS Online (SU, SUA, SUM, SURT)

Penyebab Utama:

Saat UPS sedang menyala dan tersambung ke listrik (mode online), UPS akan menghitung sisa waktu backup (runtime).
Jika waktu sisa backup kurang dari 2 menit di atas batas peringatan baterai lemah (low battery warning), maka lampu indikator baterai akan berkedip bersama-sama.

Cara Mengatasi:

1. Ubah Setting Waktu Peringatan Baterai Lemah

Misalnya: UPS punya runtime 15 menit, dan peringatan low battery diset ke 7 menit.
Jika runtime turun ke 8 menit, maka lampu baterai akan berkedip.

Solusinya: ubah setting low battery warning ke angka lebih kecil, misalnya 2 menit (bisa dilakukan lewat software PowerChute).
Catatan: PowerChute Business Edition default ke 5 menit, tidak bisa diubah.

2. Kurangi Beban atau Ganti Baterai

  • Beban berat = runtime berkurang

  • Baterai tua = kapasitas turun

Kalau runtime UPS terlalu pendek, UPS akan anggap baterai habis meskipun terlihat 100%.
Coba:

  • Kurangi perangkat yang terhubung (beban)

  • Ganti baterai kalau sudah tua (umur ideal baterai 3–6 tahun)

  • Tambahkan external battery pack kalau modelnya XL

3. Lakukan Kalibrasi Runtime Manual

Kalibrasi ini dilakukan tanpa software dan hanya jika runtime tidak akurat setelah ganti baterai.

Langkah-langkah:

  1. Matikan PowerChute dan cabut kabel serial

  2. Hubungkan beban minimal 30%

  3. Cabut listrik PLN, biarkan UPS menyala hingga mati sendiri

  4. Colokkan kembali ke listrik, biarkan UPS recharge penuh

Tujuan: agar sistem bisa menghitung ulang runtime secara akurat

Cara Kerja Indikator LED Baterai:

  • Terdapat 5 LED indikator baterai: 20%, 40%, 60%, 80%, 100%

  • Misalnya baterai 95%, maka hanya 4 LED yang menyala

Jika runtime terlalu dekat dengan waktu peringatan low battery, UPS akan memberi peringatan:

  • Bunyi beep cepat

  • LED baterai berkedip

  • Notifikasi di software PowerChute

Jika Masalah Belum Selesai?

Hubungi kami di apc-ups.id jika Anda ingin cek baterai pengganti resmi.

  • Tweet
Tagged under: apc, APC UPS, LED UPS Berkedip, replacement battery, UPS APC

About Davin

What you can read next

APC_Online_Double_Conversion
Cara Kerja UPS APC Online Double Conversion
UPS perlu diganti
Ini Pertanda UPS Anda Sudah Waktunya Diganti
Hindari Risiko Gangguan Listrik dengan UPS

Recent Posts

  • APC SRVSMB001: Modbus Card untuk Monitoring UPS

    Memiliki UPS yang andal saja tidak cukup jika k...
  • UPS APC SRV6KIL 6kVA: Solusi Online untuk Server & Data Center

    Ketika bisnis sudah bergantung penuh pada serve...
  • APC_Online_Double_Conversion

    Cara Kerja UPS APC Online Double Conversion

    UPS dengan teknologi online double conversion m...
  • SRTG15KXLI UPS APC 15kVA

    APC Smart-UPS Online SRTG15KXLI UPS untuk Data Center dan Industri

    Dalam dunia data center dan industri, kebutuhan...
  • UPS APC BX650LI-MS replacement

    UPS APC BX650LI-MS Sudah Discontinue, Apa Penggantinya?

    Dalam penggunaan perangkat IT seperti komputer,...



HUBUNGI KAMI SEKARANG JUGA

Isi formulir di bawah ini dan kami akan segera menghubungi Anda!

HUBUNGI KAMI

(021) 5358719 (direct line)
Email: info@apc-ups.id

SUPPORT

AKR Tower - Jl. Panjang no. 5,
Jakarta 11530 Indonesia

Open in Google Maps

SALES & MARKETING

PT. Jespro Network Rent

Jl. Kebon Jeruk Raya Komp. Kebon Jeruk Permai
Office Blok C No. 17 Jakarta 11530 Indonesia

APC UPS

© 2023 All rights reserved. By Jespro Network Rent.

TOP